A 200 MW three-phase load at 400 kV and 0.9 power factor draws about what current?
A 250 A
B 400 A
C 577 A
D 321 A
Answer: D. 321 A. I=P/(β3Vpf)=200 MW/(β3Γ400 kVΓ0.9), about 321 A.
A balanced line carries 200 A through 3 Ξ© resistance per phase. What is total three-phase copper loss?
A 120 kW
B 600 kW
C 360 kW
D 1.2 MW
Answer: C. 360 kW. Loss=3IΒ²R=3Γ200Β²Γ3=360 kW.
A 400 kV line has surge impedance 400 Ξ©. What is its SIL?
A 400 MW
B 100 MW
C 231 MW
D 800 MW
Answer: A. 400 MW. SIL=VLLΒ²/Zc=(400 kV)Β²/400 Ξ©=400 MW.
A 50 Hz line has inductance 0.1 H per phase. Its inductive reactance is about what?
A 3.14 Ξ©
B 50 Ξ©
C 314 Ξ©
D 31.4 Ξ©
Answer: D. 31.4 Ξ©. X=2ΟfL=2ΟΓ50Γ0.1β31.4 Ξ©.
In the nominal-Ο model, which ABCD value equals total series impedance Z?
A A
B C
C D
D B
Answer: D. B. For the nominal-Ο equivalent, B=Z.
For a nominal-Ο line, A and D are each approximately what?
A 1+YZ/2
B 1βYZ
C Z/Y
D Y/2Z
Answer: A. 1+YZ/2. The symmetric shunt halves combine with the series branch to give A=D=1+YZ/2.
For a long line with propagation constant Ξ³ and length β, A is what?
A sinh(Ξ³β)/Zc
B cosh(Ξ³β)
C ZcΞ³β only
D 1+Ξ³Β²
Answer: B. cosh(Ξ³β). Distributed-parameter long-line constants use hyperbolic functions.
For that long line, B is represented by which expression?
A Zc sinh(Ξ³β)
B cosh(Ξ³β)/Zc
C Ξ³β/ZcΒ²
D Zc cosh(Ξ³β)
Answer: A. Zc sinh(Ξ³β). The series transfer term is Zc sinh(Ξ³β).
The attenuation constant of a line describes what?
A Phase order
B Power factor sign
C Wave amplitude decay
D Conductor sag
Answer: C. Wave amplitude decay. It is the real part of propagation constant and measures amplitude reduction with distance.
Reactive power absorbed by a heavily loaded line is driven mainly by what?
A Shunt capacitance only
B Tower footing
C Skin effect only
D Series inductance
Answer: D. Series inductance. Inductive series reactance consumes VARs as current increases.
Which controller can provide fast dynamic shunt reactive support?
A STATCOM
B Synchronous condenser
C Shunt capacitor
D On-load tap changer
Answer: A. STATCOM. A STATCOM uses a voltage-source converter to rapidly inject or absorb reactive current.
A static VAR compensator commonly uses thyristor-controlled what?
A Tower wires
B Reactors or capacitors
C Series resistors only
D Diesel engines
Answer: B. Reactors or capacitors. An SVC varies shunt susceptance using thyristor-controlled reactors and switched capacitors.
What risk can series capacitors introduce with nearby turbine-generator shafts?
A Corona extinction
B Subsynchronous resonance
C Ferranti reversal
D Skin heating only
Answer: B. Subsynchronous resonance. Series compensation can interact with subsynchronous electrical modes.
A distance relay estimates fault location primarily from measured what?
A Frequency-to-power ratio
B Voltage-to-current ratio
C Temperature-to-sag ratio
D Torque-to-speed ratio
Answer: B. Voltage-to-current ratio. Apparent impedance V/I tends to increase with distance to a fault.
A mho relay is commonly used for which line-protection purpose?
A Distance protection
B Overtemperature only
C Oil level protection
D Frequency conversion
Answer: A. Distance protection. Its directional impedance characteristic suits transmission-line distance protection.
Pilot-wire differential protection compares what at both line ends?
A Tower heights
B Currents
C Surge impedances
D Fuel rates
Answer: B. Currents. A difference between end currents indicates an internal protected-zone fault.
Carrier-aided line protection sends what between terminal substations?
A Load energy
B Cooling water
C Protection signals
D Mechanical torque
Answer: C. Protection signals. Communication over power-line carrier helps coordinate high-speed tripping.
Why can higher tower-footing resistance increase back-flashover risk?
A Line current becomes zero
B Insulation improves
C Corona disappears
D Lightning voltage rises
Answer: D. Lightning voltage rises. A stroke can raise tower potential enough to flash across an insulator string.
Basic impulse insulation level specifies withstand against which stress?
A Steady DC current
B Standard impulse voltage
C Mechanical sag
D Fuel pressure
Answer: B. Standard impulse voltage. BIL rates insulation against specified lightning-impulse overvoltage.
Electromagnetic traveling waves on overhead lines propagate at a speed near what?
A Speed of light
B Wind speed
C Sound speed
D Water-wave speed
Answer: A. Speed of light. Propagation speed is a large fraction of light speed in air.
Two identical parallel lines share load equally when their impedances and terminal conditions are what?
A Opposite polarity
B Open circuited
C Matched
D At different frequencies
Answer: C. Matched. Equal impedances under the same endpoints lead to equal current sharing.
A phase-shifting transformer can redistribute power by changing what network quantity?
A Conductor area
B System frequency
C Voltage phase angle
D Line resistance
Answer: C. Voltage phase angle. Changing phase displacement changes active power flow across paths.
A series capacitor increases transfer capability mainly by reducing what in the power-angle relation?
A Bus frequency
B Generator pole count
C Load power factor only
D Series reactance
Answer: D. Series reactance. The ideal transfer limit varies inversely with series reactance.
For a lossless line, raising transfer above SIL tends to make its midpoint voltage do what?
A Sag
B Swell
C Stay exactly flat
D Become DC
Answer: A. Sag. The line absorbs reactive power above SIL, tending to depress the voltage profile.
A sudden load rejection on a long line can cause what voltage concern?
A Zero line capacitance
B Permanent frequency doubling
C Temporary overvoltage
D Negative resistance
Answer: C. Temporary overvoltage. Reduced loading can expose capacitive charging and raise receiving-end voltage.