A three-phase transformer bank can be assembled from how many single-phase units?
A One only
B Two only
C Three
D Six always
Answer: C. Three. Three single-phase transformers can form a three-phase bank.
In a balanced star winding, phase voltage equals line voltage divided by what?
A 2
B 3
C √3
D √2
Answer: C. √3. For a star connection, VL=√3Vphase.
In a balanced delta winding, phase voltage equals what?
A Line voltage/√3
B Zero
C Line voltage
D Three times line voltage
Answer: C. Line voltage. Each delta phase is connected directly across a pair of line terminals.
In a balanced star winding, line current equals what?
A Phase current
B √3 times phase current
C Phase current/3
D Zero
Answer: A. Phase current. Each line conductor is in series with its phase winding.
In a balanced delta winding, line current magnitude is what relative to phase current?
A Equal to
B One third of
C Three times
D √3 times
Answer: D. √3 times. The phasor difference of two phase currents has magnitude √3Iphase.
A 400 V balanced star winding has approximately what phase voltage?
A 400 V
B 693 V
C 231 V
D 133 V
Answer: C. 231 V. 400/√3 is about 231 V.
A 400 V balanced delta winding has what voltage across each phase?
A 231 V
B 693 V
C 400 V
D 200 V
Answer: C. 400 V. In delta, each winding is directly across the 400 V line voltage.
A star connection makes which conductor available if the neutral point is brought out?
A Neutral
B Commutator
C Rotor
D Slip ring
Answer: A. Neutral. The common junction of the three phase windings can supply a neutral.
Why is a closed delta winding helpful for triplen harmonic currents?
A Raises input frequency
B Provides circulating path
C Stops all core loss
D Creates DC output
Answer: B. Provides circulating path. Zero-sequence triplen components can circulate within the delta rather than appear in line current.
An open-delta bank using two of three identical units has about what fraction of its original closed-delta kVA?
A 57.7%
B 100%
C 33.3%
D 86.6%
Answer: A. 57.7%. Open-delta capacity is √3 times one unit, versus 3 times one unit originally.
What does a transformer vector group identify?
A Oil volume only
B Connection and phase shift
C Core temperature only
D Winding resistance only
Answer: B. Connection and phase shift. It specifies winding connection and clock-hour phase displacement.
Parallel transformers should have closely matched voltage ratios to avoid what?
A Circulating current
B Core lamination
C Neutral conductor
D Rated frequency
Answer: A. Circulating current. Unequal no-load secondary voltages drive current between parallel units.
Which polarity condition is necessary before paralleling transformer secondaries?
A Matching polarity
B Opposite polarity
C Random polarity
D No polarity marks
Answer: A. Matching polarity. Wrong polarity can connect unlike potentials together and cause a severe circulating current.
For three-phase transformers in parallel, their phase sequence and phase displacement should be what?
A Always opposite
B Random
C Unmeasured
D Compatible
Answer: D. Compatible. Matching phase relationships prevent large circulating currents.
With equal ratios, which transformer tends to carry more current if its equivalent impedance is lower?
A Higher-impedance unit
B Lower-impedance unit
C Neither unit
D Only the neutral
Answer: B. Lower-impedance unit. Parallel current divides inversely with equivalent impedance.
Why does equal percentage impedance aid proportional load sharing for unequal kVA ratings?
A Equal turn counts
B Zero losses
C Identical tank size
D Similar per-unit drops
Answer: D. Similar per-unit drops. At common voltage, equal per-unit impedance lets each unit share in proportion to rating.
A transformer may draw a large transient current when first energized. What is it called?
A Copper regulation
B Magnetizing inrush
C Creeping
D Mechanical stall
Answer: B. Magnetizing inrush. Core flux transients and saturation can cause high inrush current.
Differential relays often use which harmonic component to restrain during magnetizing inrush?
A Fundamental only
B Fifth only
C Second harmonic
D Zero frequency
Answer: C. Second harmonic. Inrush current often contains a strong second harmonic, used by conventional restraint schemes.
What is the principal protection zone of transformer differential protection?
A Entire power grid
B Only outgoing feeder
C Ambient enclosure
D Internal winding region
Answer: D. Internal winding region. A differential relay compares currents entering and leaving its defined transformer zone.
An overcurrent relay can serve as what for transformer external faults?
A Oil conservator
B Tap selector
C Core monitor only
D Backup protection
Answer: D. Backup protection. Overcurrent protection can clear faults when primary protection does not operate.
Before comparing three-phase transformer currents in a differential relay, what may need compensation?
A Paint and tank size
B Frequency doubling
C Shaft position
D Ratio and phase shift
Answer: D. Ratio and phase shift. Current-transformer scaling and connection compensate the transformer ratio and phase displacement.
A neutral grounding connection mainly helps provide a path for what fault current?
A Earth fault current
B Only load harmonics
C Mechanical friction
D Core eddy current
Answer: A. Earth fault current. Grounding establishes a return path and reference for ground-fault detection.
Balanced three-phase apparent power equals which expression using line values?
A √3 VL IL
B VL/IL
C 3 VL/IL
D VL IL/√3
Answer: A. √3 VL IL. The three-phase apparent-power magnitude is √3 times line voltage times line current.
At 400 V line voltage and 10 A line current, apparent power is about what?
A 4 kVA
B 6.93 kVA
C 40 kVA
D 0.69 kVA
Answer: B. 6.93 kVA. √3×400×10≈6928 VA, or 6.93 kVA.
What is the usual effect of an unintended phase displacement mismatch when paralleling three-phase units?
A Perfect sharing
B Large circulating currents
C Zero magnetizing current
D Frequency change
Answer: B. Large circulating currents. Unlike secondary phase voltages oppose each other across a low-impedance loop.