Which transformer loss exists even when the secondary is open?
A Core loss
B Full-load copper loss
C Load stray loss
D Brush friction
Answer: A. Core loss. Alternating core flux produces iron loss at rated applied voltage.
Winding copper loss varies mainly with which quantity?
A Voltage squared only
B Frequency only
C Core flux only
D Current squared
Answer: D. Current squared. Resistive winding heating follows I²R.
Which magnetic process causes hysteresis loss?
A Static DC resistance
B Shaft friction
C Repeated magnetization
D Brush commutation
Answer: C. Repeated magnetization. The iron’s flux density cycles through a hysteresis loop under AC excitation.
What is the chief electrical effect of leakage flux in the equivalent circuit?
A Core-loss resistance
B Ideal turns ratio
C Leakage reactance
D Insulation capacitance only
Answer: C. Leakage reactance. Flux that does not link both windings contributes series leakage inductance.
Where are winding resistances represented in the approximate equivalent circuit?
A Series branches
B Shunt core branch
C Across the tank
D Across the load only
Answer: A. Series branches. Primary and secondary copper losses are modeled by series resistances.
Where is the exciting branch placed in a transformer equivalent circuit?
A In series with load
B Across each winding turn
C In the oil tank
D Across the input
Answer: D. Across the input. The magnetizing and core-loss currents are represented by a shunt branch.
The resistance Rc in the excitation branch models what?
A Core loss
B Load copper loss
C Leakage flux
D Turn ratio
Answer: A. Core loss. Real power consumed by the core is represented by Rc.
The reactance Xm in the excitation branch models what?
A Magnetizing current
B Brush drop
C Winding heating
D Load resistance
Answer: A. Magnetizing current. Xm accounts for current that establishes alternating mutual flux.
In a standard open-circuit test, what is done to the secondary winding?
A Left open
B Shorted directly
C Loaded at rated kVA
D Connected to DC
Answer: A. Left open. With the other winding open, rated voltage draws only no-load current.
The open-circuit test wattmeter reading approximately gives which loss?
A Full-load copper loss
B Core loss
C Bearing friction
D Stray-load loss
Answer: B. Core loss. Low no-load current makes winding copper loss small compared with iron loss.
Which side is commonly energized at rated voltage for an open-circuit test?
A High-voltage side only
B Low-voltage side
C Both sides simultaneously
D Neither side
Answer: B. Low-voltage side. Energizing the LV winding makes rated test voltage easier to supply and measure.
In a short-circuit test, what is done to one transformer winding?
A Shorted
B Left open
C Connected to capacitor
D Driven by DC
Answer: A. Shorted. One side is shorted while reduced voltage is applied to the other.
Why is only a small applied voltage needed in a short-circuit test?
A No core present
B Zero rated current
C Low series impedance
D Infinite turns ratio
Answer: C. Low series impedance. The shorted winding draws rated current at a fraction of rated voltage.
At rated test current, the short-circuit wattmeter reading approximately gives what?
A Rated core loss only
B Mechanical loss
C Full-load copper loss
D Dielectric strength
Answer: C. Full-load copper loss. Small applied voltage gives little flux and core loss, leaving winding I²R loss dominant.
How is equivalent impedance magnitude found from short-circuit test voltage Vsc and current Isc?
A Vsc×Isc
B Vsc/Isc
C Isc/Vsc
D Vsc²Isc
Answer: B. Vsc/Isc. The applied voltage divided by measured current gives equivalent impedance.
Percentage impedance is the short-circuit voltage for rated current expressed relative to what?
A Rated frequency
B Core loss
C Rated voltage
D No-load current
Answer: C. Rated voltage. Z% is 100 times Vsc divided by the corresponding rated voltage.
A transformer needs 23 V short-circuit voltage on a 230 V rated winding. What is its percentage impedance?
A 10%
B 1%
C 23%
D 100%
Answer: A. 10%. 23/230×100=10%.
To refer a secondary resistance to the primary, multiply it by what if a=Np/Ns?
A a
B a²
C 1/a
D 1/a²
Answer: B. a². Impedance and resistance scale by the square of turns ratio.
Primary-referred series resistance includes R1 plus what?
A R2/a
B aR2²
C Xm
D a²R2
Answer: D. a²R2. The secondary winding resistance referred to primary is a²R2.
A transformer at no load typically has which power factor?
A Exactly unity
B Leading at all voltages
C Negative always
D Low and lagging
Answer: D. Low and lagging. The no-load current is dominated by its magnetizing component.
For a lagging load, approximate voltage drop involves which combination?
A Rcosφ−Xsinφ
B R/X only
C R+X²
D Rcosφ+Xsinφ
Answer: D. Rcosφ+Xsinφ. Resistive and reactive drops both contribute positively to lagging-load regulation.
For a leading load, approximate voltage drop contains which reactance term?
A Positive Xsinφ
B Zero always
C Negative Xsinφ
D X²cosφ
Answer: C. Negative Xsinφ. The leading current’s reactive component can offset the resistive voltage drop.
Ignoring source impedance, a transformer with 5% impedance has a prospective short-circuit current about how many times rated?
A 5 times
B 20 times
C 2 times
D 100 times
Answer: B. 20 times. 1/0.05=20 per unit for an ideal stiff source.
Which test is used mainly to obtain the shunt excitation-branch parameters?
A Short-circuit test
B Polarity test only
C Oil test only
D Open-circuit test
Answer: D. Open-circuit test. No-load V, I and power yield core-loss resistance and magnetizing reactance.
Which test is used mainly to obtain series equivalent impedance?
A Open-circuit test
B Short-circuit test
C Temperature test only
D Turns count only
Answer: B. Short-circuit test. Rated-current short-circuit data yields series resistance and reactance.