Voltage regulation compares no-load and loaded secondary voltages at fixed primary voltage. Which expression is usual?
A (Vfl−Vnl)/Vnl
B Vnl×Vfl
C (Vnl−Vfl)/Vfl
D Vfl/Vnl²
Answer: C. (Vnl−Vfl)/Vfl. The difference is divided by full-load terminal voltage and often stated as a percentage.
A transformer at lagging power factor usually has what sign of voltage regulation?
A Positive
B Always negative
C Exactly zero
D Undefined
Answer: A. Positive. Series impedance drop usually makes full-load voltage lower than no-load voltage.
At a sufficiently leading power factor, transformer regulation can be what?
A Always positive
B Always infinite
C Equal to frequency
D Negative
Answer: D. Negative. The leading reactive drop can cause loaded terminal voltage to rise.
No-load secondary voltage is 220 V and full-load is 200 V. What is regulation based on full-load voltage?
A 10%
B 9.09%
C 20%
D 110%
Answer: A. 10%. (220−200)/200×100=10%.
Transformer efficiency is useful output power divided by what?
A Input power
B Rated kVA only
C Core flux
D No-load current
Answer: A. Input power. Efficiency compares delivered real power with real input power.
A transformer receives 10 kW and delivers 9 kW. What is total loss?
A 9 kW
B 1 kW
C 10 kW
D 19 kW
Answer: B. 1 kW. Loss is input minus output, or 1 kW.
Maximum efficiency occurs approximately when variable copper loss equals what?
A Core loss
B Output kVA
C Load current
D Leakage reactance
Answer: A. Core loss. The load-dependent copper loss balances the approximately constant iron loss.
At constant applied voltage and frequency, core loss is approximately what as load changes?
A Proportional to load²
B Always zero
C Constant
D Equal to output
Answer: C. Constant. Core flux stays nearly fixed, so iron loss is roughly constant.
Copper loss at half rated current is what fraction of rated-current copper loss?
A One half
B One quarter
C Two times
D Four times
Answer: B. One quarter. I²R at 0.5 rated current is 0.25 of rated loss.
All-day efficiency compares what over a 24-hour load cycle?
A Peak and RMS current
B Rated and actual frequency
C Output and input energy
D Turn counts
Answer: C. Output and input energy. Energy efficiency reflects varying load throughout the day.
Which application makes all-day efficiency especially useful?
A Constant full-load motor
B Brushless DC drive
C Synchronous generator
D Distribution transformer
Answer: D. Distribution transformer. Distribution transformers remain energized while their daily load varies.
A tap changer adjusts output voltage by changing what?
A Supply frequency
B Core material
C Oil viscosity
D Effective turns ratio
Answer: D. Effective turns ratio. Selecting winding taps changes the active number of turns.
What distinguishes an on-load tap changer?
A Requires permanent shutdown
B Changes frequency
C Changes taps under load
D Shorts both windings
Answer: C. Changes taps under load. It transfers between taps while maintaining supply to the load.
When should an off-circuit tap changer normally be operated?
A With transformer de-energized
B At peak load
C During short circuit
D Only at no-load current
Answer: A. With transformer de-energized. An off-circuit tap changer is not designed to interrupt load current.
At fixed primary voltage and secondary turns, reducing active primary turns tends to do what to secondary voltage?
A Decrease it
B Increase it
C Make it zero
D Change frequency
Answer: B. Increase it. Vs/Vp=Ns/Np, so a smaller Np raises Vs.
An autotransformer differs from a two-winding transformer because its windings have what?
A No magnetic core
B A common electrical section
C Two isolated circuits
D A rotating armature
Answer: B. A common electrical section. Part of one winding serves both input and output circuits.
Does an ordinary autotransformer provide galvanic isolation between input and output?
A Yes, always
B Only at rated load
C Only with DC
D No
Answer: D. No. Its shared winding creates a direct conductive connection.
Why can an autotransformer use less copper for a modest voltage-ratio change?
A It eliminates core flux
B It has no current
C Part power transfers conductively
D It changes frequency
Answer: C. Part power transfers conductively. A common winding carries only part of the total transferred power magnetically.
Which transformer type provides separate primary and secondary circuits for isolation?
A Autotransformer
B Two-winding transformer
C Tapped wire only
D Series reactor
Answer: B. Two-winding transformer. Independent windings are coupled magnetically without a direct conductor.
Transformer oil in an oil-filled unit serves mainly as insulation and what else?
A Mechanical lubricant for shaft
B Fuel
C Cooling medium
D Frequency converter
Answer: C. Cooling medium. Oil transfers heat from windings and core while insulating live parts.
What is the purpose of a conservator on an oil-filled transformer?
A Allow oil expansion
B Change turns ratio
C Measure load current
D Short fault current
Answer: A. Allow oil expansion. The conservator accommodates oil-volume changes with temperature.
A silica-gel breather chiefly reduces what entering a conservator-type unit?
A Moisture
B Magnetic flux
C Primary voltage
D Copper loss
Answer: A. Moisture. It dries air drawn into the conservator as oil level changes.
A Buchholz relay is intended to detect what in a conservator-type oil transformer?
A External line frequency
B Tap position only
C Ambient wind speed
D Internal fault gases
Answer: D. Internal fault gases. Gas generated by an internal fault accumulates in the relay chamber.
Transformer differential protection compares currents on which sides?
A Only two phases
B Only the neutral
C Only the core
D Input and output
Answer: D. Input and output. After ratio and phase compensation, a mismatch indicates an internal fault.
If output is 9 kW and total loss is 1 kW, what is efficiency?
A 10%
B 90%
C 100%
D 111%
Answer: B. 90%. Input is 10 kW, so η=9/10=90%.