Before closing an alternator breaker onto a live bus, which set of quantities should match?
A Voltage, frequency, phase sequence
B Only shaft torque
C Only current magnitude
D Only field resistance
Answer: A. Voltage, frequency, phase sequence. Synchronization requires compatible voltage, frequency, phase order and phase angle.
An incoming generator frequency should be how relative to the bus before synchronizing?
A Nearly equal
B Twice as high
C Zero
D Exactly negative
Answer: A. Nearly equal. A small frequency difference permits the phase angle to approach coincidence.
Why must incoming phase sequence match the bus phase sequence?
A Increase core loss
B Reduce pole count
C Correct phase pairing
D Raise field resistance
Answer: C. Correct phase pairing. Opposite phase order cannot be synchronized by waiting for phase coincidence.
Closing with the wrong phase sequence can cause what?
A Severe currents and torque
B Perfect load sharing
C Zero stator current
D A frequency converter
Answer: A. Severe currents and torque. Unlike phase voltages are effectively connected across low impedance.
What does a synchroscope indicate about an incoming alternator?
A Relative phase and frequency
B Core temperature only
C Rotor winding resistance
D Oil level
Answer: A. Relative phase and frequency. Its pointer indicates phase difference and the direction/rate of slip.
In a correctly arranged three-dark-lamp synchronizing method, when do all lamps darken together?
A At maximum phase difference
B Near voltage coincidence
C Only at zero speed
D Whenever power factor is zero
Answer: B. Near voltage coincidence. Simultaneous darkness indicates small voltage differences across breaker contacts.
The synchronizing breaker should close when incoming and bus voltages are approximately what?
A 180° apart
B At different frequencies
C In phase
D Opposite sequence
Answer: C. In phase. Near phase coincidence minimizes transient current and torque.
After two alternators are paralleled, what mainly increases one generator’s real-power share?
A Field current alone
B Stator resistance
C Cooling air flow
D Prime-mover input
Answer: D. Prime-mover input. Greater mechanical torque increases its power angle and active output.
After paralleling, what mainly adjusts one generator’s reactive-power share?
A Prime-mover fuel only
B Rotor pole count
C Bearing friction
D Field excitation
Answer: D. Field excitation. Changing excitation changes internal EMF and reactive current.
An overexcited synchronous generator usually does what with reactive power?
A Always absorbs it
B Supplies it to bus
C Produces no VAR
D Changes frequency only
Answer: B. Supplies it to bus. Stronger field excitation tends to inject reactive power.
An underexcited synchronous generator on a grid tends to do what with reactive power?
A Absorb it
B Always supply it
C Make it zero
D Reverse phase sequence
Answer: A. Absorb it. Reduced excitation tends to draw reactive power from the system.
What does an ideal infinite bus hold nearly fixed despite one machine’s small changes?
A Rotor copper loss
B Pole count
C Voltage and frequency
D Shaft torque
Answer: C. Voltage and frequency. A large grid sets bus voltage and frequency.
With generator mechanical power held constant on an infinite bus, raising excitation mainly changes what?
A System frequency
B Reactive power
C Rotor pole count
D Prime-mover speed
Answer: B. Reactive power. Field adjustment primarily alters VAR flow and power factor.
With excitation fixed on an infinite bus, raising prime-mover torque mainly increases what?
A Grid frequency
B Field resistance
C Cooling airflow
D Real power output
Answer: D. Real power output. The rotor load angle increases and transfers more active power.
Which control normally adjusts prime-mover input to regulate generator active power or frequency?
A Automatic voltage regulator
B Differential relay
C Surge arrester
D Governor
Answer: D. Governor. The governor changes turbine or engine input.
Which control normally regulates terminal voltage by adjusting excitation?
A Governor
B Oil conservator
C Shaft encoder only
D AVR
Answer: D. AVR. An automatic voltage regulator controls field current.
Generator droop settings help multiple units share which service?
A Only bearing friction
B Only insulation loss
C Only core saturation
D Load and frequency response
Answer: D. Load and frequency response. Droop enables stable proportional response among parallel generators.
A reverse-power relay protects a generator when its prime mover fails by detecting what?
A Higher field resistance
B Oil expansion
C Motoring power flow
D Extra poles
Answer: C. Motoring power flow. The generator can draw real power from the bus and act as a motor.
A loss-of-excitation relay responds chiefly to what?
A High oil level
B Low shaft friction
C Abnormally low field
D Extra phase winding
Answer: C. Abnormally low field. Field failure can make a generator absorb VAR and risk instability.
An out-of-step condition means the rotor has done what?
A Lost synchronism
B Gained pole count
C Stopped all stator current
D Reversed phase sequence
Answer: A. Lost synchronism. The rotor no longer remains locked to the system rotating field.
What is a likely result of closing a generator breaker at a large phase-angle mismatch?
A Transient current and torque
B No disturbance
C Guaranteed zero current
D Lower supply frequency
Answer: A. Transient current and torque. The instantaneous voltage difference drives a surge and mechanical stress.
Parallel generator operation lets multiple units do what?
A Eliminate all losses
B Avoid synchronization
C Share a common load
D Remove excitation
Answer: C. Share a common load. Units together supply demand and allow flexible operation.
In generator operation, internal EMF E is usually positioned how relative to terminal voltage V in power angle?
A E always lags V
B E leads V
C E equals zero
D E is 180° apart
Answer: B. E leads V. Generator rotor field leads the resultant field in the simple power-angle model.
For the idealized cylindrical-rotor P∝sinδ model, maximum power occurs near which angle?
A 0°
B 90°
C 30°
D 180°
Answer: B. 90°. The sine function peaks at δ=90 electrical degrees.
A bus-connected generator whose prime-mover input falls too far may draw real power and act as what?
A A transformer
B A motor
C A capacitor only
D An open circuit
Answer: B. A motor. The grid can drive its rotor when mechanical input is inadequate.