In a generator model, the internal generated EMF differs from terminal voltage because of what?
A Pole count change
B Internal impedance drop
C Shaft friction only
D Frequency doubling
Answer: B. Internal impedance drop. Armature resistance and synchronous reactance create internal phasor drops.
Synchronous reactance combines leakage reactance with an equivalent effect of what?
A Bearing friction
B Armature reaction
C Field copper loss
D Oil cooling
Answer: B. Armature reaction. The model represents armature reaction and leakage flux as a reactance.
Armature resistance primarily represents which electrical loss?
A Rotor windage
B Core saturation
C Mechanical friction
D Stator copper loss
Answer: D. Stator copper loss. Current through stator winding resistance dissipates I²R.
For a generator, which approximate phasor relation uses terminal voltage V and armature current I?
A E=V+(Ra+jXs)I
B E=V−(Ra+jXs)I
C E=VI/Xs
D E=I/Ra
Answer: A. E=V+(Ra+jXs)I. The generator internal EMF equals terminal voltage plus its series impedance drop.
Which voltage-regulation expression uses no-load voltage E0 and full-load terminal voltage V?
A (V−E0)/E0
B (E0−V)/V
C E0×V
D V/E0²
Answer: B. (E0−V)/V. Regulation compares the no-load value with the loaded terminal value.
If no-load voltage is 230 V and full-load voltage is 200 V, what is regulation?
A 13%
B 30%
C 115%
D 15%
Answer: D. 15%. (230−200)/200×100=15%.
At unity power factor, armature reaction of a simple alternator is mainly what?
A Purely demagnetizing
B Purely magnetizing
C Cross-magnetizing
D Exactly zero
Answer: C. Cross-magnetizing. The armature field mainly distorts the main flux at unity power factor.
At strongly lagging power factor, armature reaction tends mainly to do what?
A Magnetize
B Eliminate leakage
C Demagnetize
D Raise frequency
Answer: C. Demagnetize. Lagging armature current opposes much of the main field flux.
At strongly leading power factor, armature reaction tends mainly to do what?
A Magnetize
B Demagnetize
C Stop the rotor
D Reduce pole count
Answer: A. Magnetize. Leading armature current reinforces the main field component.
As field current becomes high, why does the OCC slope decrease?
A Shaft speed zero
B Zero armature turns
C Negative frequency
D Core saturation
Answer: D. Core saturation. Additional excitation produces less extra flux as the iron saturates.
At the same field current, open-circuit EMF divided by short-circuit current gives what?
A Armature resistance only
B Shaft torque
C Power factor
D Synchronous impedance
Answer: D. Synchronous impedance. The synchronous impedance method uses Zs≈Eoc/Isc per phase.
Short-circuit ratio compares field current for rated open-circuit voltage with field current for what?
A Rated short-circuit current
B Zero current
C Maximum torque
D Rated shaft speed
Answer: A. Rated short-circuit current. SCR is If for rated OCC voltage divided by If for rated SCC current.
A higher short-circuit ratio generally indicates what about synchronous reactance?
A Infinite reactance
B Zero field current
C Higher pole count
D Lower reactance
Answer: D. Lower reactance. Higher SCR usually corresponds to lower per-unit synchronous reactance.
The zero-power-factor test helps account for saturation and leakage in which construction?
A Wheatstone bridge
B Kelvin bridge
C Potier triangle
D Swinburne test
Answer: C. Potier triangle. Potier analysis separates leakage and armature-reaction effects using the ZPF characteristic.
A slip test on a salient-pole machine can estimate which pair?
A Xd and Xq
B Ra and bearing loss
C Core and copper loss
D Pole count and speed
Answer: A. Xd and Xq. Variation of armature response with rotor angle reveals direct and quadrature reactances.
The direct axis of a salient-pole rotor is aligned with what?
A Interpolar centerline
B Shaft bearing
C Pole centerline
D Stator terminal
Answer: C. Pole centerline. The d-axis runs through the magnetic pole centers.
The quadrature axis is displaced from the direct axis by how many electrical degrees?
A 30°
B 90°
C 120°
D 180°
Answer: B. 90°. The q-axis is electrically perpendicular to the d-axis.
For a typical salient-pole machine, how do synchronous reactances compare?
A Xd equals zero
B Xq exceeds Xd always
C Xd exceeds Xq
D Both are negative
Answer: C. Xd exceeds Xq. The pole axis has a smaller air gap and generally higher inductance.
Three-phase stator copper loss is approximately which expression?
A Ia/Ra
B 3Ia²Ra
C 3IaRa²
D Ra/3Ia
Answer: B. 3Ia²Ra. Each phase dissipates Ia²Ra.
Three-phase real power at line voltage VL, line current IL and power factor cosφ equals what?
A √3VLILcosφ
B VL/IL
C 3VLIL/sinφ
D VLIL/√3
Answer: A. √3VLILcosφ. Balanced three-phase real power is √3 times line voltage, current and power factor.
Three-phase reactive power at line values equals what?
A √3VLILsinφ
B VLILcosφ
C IL/VL
D 3VL/IL
Answer: A. √3VLILsinφ. Balanced three-phase reactive power is √3VLILsinφ.
At 400 V, 10 A and 0.8 power factor, real three-phase power is about what?
A 4.0 kW
B 5.54 kW
C 6.93 kW
D 8.0 kW
Answer: B. 5.54 kW. √3×400×10×0.8≈5.54 kW.
Alternator efficiency compares electrical output to what?
A Reactive output
B Field current only
C Mechanical input
D Synchronous speed
Answer: C. Mechanical input. Efficiency is useful electrical power divided by total mechanical input, accounting for losses.
Why can a leading-load alternator have negative voltage regulation?
A Terminal voltage may rise
B Core loss becomes zero
C Frequency reverses
D Pole count changes
Answer: A. Terminal voltage may rise. A leading armature reaction can raise loaded terminal voltage above the corresponding no-load value.
In the idealized cylindrical-rotor power-angle model, power varies approximately with what?
A cos²δ
B 1/δ
C δ² only
D sinδ
Answer: D. sinδ. Ignoring resistance, the transferred power is proportional to sin of the load angle.