A 1 MW three-phase load on 11 kV at 0.8 power factor draws about what current?
A 65.6 A
B 45.5 A
C 100 A
D 131 A
Answer: A. 65.6 A. I=P/(β3Vpf)=1,000,000/(β3Γ11,000Γ0.8)β65.6 A.
A 100 kVA three-phase transformer has a 415 V secondary. Its rated current is about what?
A 58 A
B 100 A
C 139 A
D 241 A
Answer: C. 139 A. I=S/(β3V)=100,000/(β3Γ415)β139 A.
A feeder carries 100 A at 0.8 lagging pf, with R=0.2 Ξ© and X=0.3 Ξ© per phase. Approximate line drop?
A 59 V
B 34 V
C 83 V
D 100 V
Answer: A. 59 V. ΞVββ3I(RcosΟ+XsinΟ)=β3Γ100Γ(0.16+0.18)β59 V.
A balanced feeder has 0.2 Ξ© resistance per phase and 100 A current. What is total copper loss?
A 6 kW
B 2 kW
C 20 kW
D 60 kW
Answer: A. 6 kW. P_loss=3IΒ²R=3Γ100Β²Γ0.2=6000 W.
A 100 kW load is corrected from 0.8 to 0.95 power factor. Required capacitor size is about what?
A 42 kvar
B 20 kvar
C 75 kvar
D 100 kvar
Answer: A. 42 kvar. Qc=P(tanΟ1βtanΟ2)=100(0.75β0.329)β42 kvar.
A 2 MW three-phase load at 11 kV and 0.9 power factor draws about what current?
A 117 A
B 58 A
C 182 A
D 350 A
Answer: A. 117 A. I=2,000,000/(β3Γ11,000Γ0.9)β117 A.
A 250 kVA transformer supplies a load at 0.8 power factor. Real power is what?
A 125 kW
B 200 kW
C 250 kW
D 312.5 kW
Answer: B. 200 kW. P=SΓpf=250Γ0.8=200 kW.
Why can a feeder with high distributed-generation penetration need directional protection?
A Resistance becomes zero
B Frequency doubles
C Loads disappear
D Power may reverse
Answer: D. Power may reverse. Local generation can reverse current direction during faults and normal export.
What does a distribution sectionalizer do during an upstream recloser dead time?
A Clears fault current itself
B Isolates counted fault section
C Raises feeder voltage
D Changes phase sequence
Answer: B. Isolates counted fault section. It opens after counting upstream interruptions while the circuit is de-energized.
A fuse-saving scheme aims for the recloser to do what on a temporary fault?
A Wait for fuse always
B Trip every feeder
C Remain permanently open
D Fast trip first
Answer: D. Fast trip first. A fast upstream shot may clear a transient before a lateral fuse melts.
When selective fuse coordination is preferred, which device should clear a lateral fault first?
A Substation transformer
B All feeder relays
C Generator breaker
D Lateral fuse
Answer: D. Lateral fuse. The branch fuse isolates only the affected lateral.
A three-phase feeder carries 100 A with 0.5 Ξ© resistance per phase. Total IΒ²R loss equals what?
A 15 kW
B 5 kW
C 50 kW
D 150 kW
Answer: A. 15 kW. 3Γ100Β²Γ0.5=15,000 W.
For a grounded-wye secondary, which current component sums in the neutral during unbalance?
A Balanced positive sequence
B Line-to-line voltage
C Residual phase current
D Transformer flux
Answer: C. Residual phase current. The neutral carries the phasor sum of phase currents.
Why can third-harmonic currents add in the neutral of a four-wire system?
A They are 120Β° apart
B They are DC-free
C They cancel pairwise
D They are in phase
Answer: D. They are in phase. Triplen harmonics are zero-sequence and add arithmetically in the neutral.
An OLTC changes taps while maintaining what?
A Open circuit
B Customer supply
C Zero current
D Fixed transformer ratio
Answer: B. Customer supply. It transitions between taps while carrying load.
A voltage regulator set point is 1.0 pu. What voltage is this relative to nominal?
A 10%
B 50%
C 100%
D 200%
Answer: C. 100%. One per unit equals rated or nominal voltage.
A feeder has SAIFI=4 interruptions/customer-year. For 100 customers, how many customer interruptions occurred?
A 25
B 100
C 4000
D 400
Answer: D. 400. Total customer interruptions=4Γ100=400.
A utility records 900 customer-hours of interruption for 300 customers. SAIDI is what?
A 0.33 hours/customer
B 300 hours/customer
C 3 hours/customer
D 900 hours/customer
Answer: C. 3 hours/customer. SAIDI=900/300=3 hours per customer.
If SAIDI is 8 hours/customer and SAIFI is 4 interruptions/customer, CAIDI is what?
A 4 hours/interruption
B 8 hours/interruption
C 32 hours/interruption
D 2 hours/interruption
Answer: D. 2 hours/interruption. CAIDI=SAIDI/SAIFI=8/4=2 hours.
A high-resistance fault may challenge ordinary overcurrent protection because fault current can be what?
A Always infinite
B Exactly rated
C Relatively low
D Purely reactive
Answer: C. Relatively low. High fault resistance can limit current below a simple overcurrent pickup.
A capacitor bank switched onto an energized feeder can create what transient?
A Mechanical torque
B Inrush current
C DC generation
D Lower insulation stress always
Answer: B. Inrush current. Capacitor energization can produce a brief current and voltage transient.
A feeder voltage sag during a nearby fault is mainly due to what?
A Change in conductor material
B Current through source impedance
C Lower system frequency only
D Transformer turns increase
Answer: B. Current through source impedance. Fault current creates a voltage drop across upstream impedance.
A distributed generator can raise local voltage when exporting power because what changes?
A Line resistance vanishes
B Voltage becomes DC
C Feeder drop reverses
D Neutral opens always
Answer: C. Feeder drop reverses. Power export can reverse the normal voltage-drop direction along the feeder.
An earth-fault relay often detects which quantity?
A Positive-sequence voltage only
B Residual current
C Active energy
D Transformer oil level
Answer: B. Residual current. Earth faults create a current imbalance measurable as residual or zero-sequence current.
During outage restoration, a normally open tie switch helps by transferring what?
A Load to healthy feeder
B Fault current to ground
C Generator fuel
D Transformer core flux
Answer: A. Load to healthy feeder. The tie can re-energize isolated customers from another feeder source.