Distribution Systems MCQs (Set-2)

Balanced three-phase real power is calculated from line values using which formula?

A VLIL only
B 3VL/IL
C VL/√3IL
D √3VLILcosΟ†

A 415 V three-phase load draws 100 A at 0.8 power factor. What is real power, approximately?

A 33.2 kW
B 72.0 kW
C 83.0 kW
D 57.5 kW

A 100 kW single-phase load at 240 V and unity power factor draws what current?

A 240 A
B 417 A
C 100 A
D 577 A

A 24 kW single-phase load operates at 240 V and unity power factor. What is current?

A 24 A
B 58 A
C 240 A
D 100 A

A 500 kVA transformer has an 11 kV three-phase primary. Rated primary current is about what?

A 45.5 A
B 500 A
C 26.2 A
D 1100 A

A 500 kVA transformer has a 415 V three-phase secondary. Rated secondary current is about what?

A 120 A
B 500 A
C 696 A
D 1205 A

Distribution conductor loss under balanced loading is proportional to what?

A Current squared
B Voltage only
C Frequency only
D Power factor angle only

Distribution transformer capacity is normally stated in what units?

A kW only
B kWh
C Hz
D kVA

A 100 kVA load at 0.8 power factor consumes how much real power?

A 20 kW
B 80 kW
C 100 kW
D 125 kW

Along a loaded radial feeder, voltage magnitude generally does what with distance from source?

A Rises without limit
B Becomes DC
C Stays exactly fixed
D Falls

In a four-wire feeder, neutral current is mainly due to what?

A Phase-load imbalance
B Balanced phase currents
C Line frequency
D Transformer core loss

A three-phase four-wire system can supply which combination?

A Three-phase and single-phase loads
B Only DC loads
C Only balanced motors
D Single voltage only

A ring-main network is often operated with one point open to obtain what?

A Two sources in parallel always
B Radial protection behavior
C Zero voltage drop
D DC operation

A normally open tie switch can connect a feeder to what during an outage?

A Alternate supply
B Ground permanently
C Customer meter
D Generator shaft

A load-break switch is designed to interrupt what?

A Any fault current
B Lightning current only
C Normal load current
D Transformer inrush always

A disconnector or isolator is normally operated after what condition?

A Current is interrupted
B Fault current is flowing
C Load is at peak
D Voltage doubles

Why does a feeder recloser attempt a brief reclosing after a trip?

A Fault may be temporary
B It measures kWh
C It raises voltage
D It changes phase order

For fuse-recloser coordination, what is generally intended for a downstream lateral fault?

A All feeder breakers trip
B Lateral fuse clears first
C Upstream transformer trips first
D No protection operates

A phase-balancing plan tries to distribute single-phase customers how?

A On one phase only
B On the neutral
C Across three phases evenly
D Across two frequencies

A distribution capacitor bank supplies which type of power locally?

A Mechanical power
B Fuel energy
C Short-circuit power only
D Reactive power

A 200 kW load at 0.8 power factor has apparent power equal to what?

A 250 kVA
B 160 kVA
C 200 kVA
D 360 kVA

Why can low power factor raise feeder current for the same kW?

A Real power becomes zero
B Voltage doubles
C More apparent power flows
D Resistance decreases

A feeder tie point is most useful when operators need to do what?

A Increase customer voltage indefinitely
B Measure conductor sag
C Restore loads after fault
D Change system frequency

How can an energy meter help a utility identify nontechnical loss?

A Measure pole height
B Compare billed energy
C Control line frequency
D Reduce conductor resistance

Which operating change can reduce technical losses in a loaded feeder?

A Lower power factor
B Reduce unnecessary current
C Use thinner conductors
D Increase path length