Balanced three-phase real power is calculated from line values using which formula?
A VLIL only
B 3VL/IL
C VL/β3IL
D β3VLILcosΟ
Answer: D. β3VLILcosΟ. Real power equals β3 times line voltage, current and power factor.
A 415 V three-phase load draws 100 A at 0.8 power factor. What is real power, approximately?
A 33.2 kW
B 72.0 kW
C 83.0 kW
D 57.5 kW
Answer: D. 57.5 kW. P=β3Γ415Γ100Γ0.8β57.5 kW.
A 100 kW single-phase load at 240 V and unity power factor draws what current?
A 240 A
B 417 A
C 100 A
D 577 A
Answer: B. 417 A. I=P/V=100,000/240β417 A.
A 24 kW single-phase load operates at 240 V and unity power factor. What is current?
A 24 A
B 58 A
C 240 A
D 100 A
Answer: D. 100 A. I=P/V=24,000/240=100 A.
A 500 kVA transformer has an 11 kV three-phase primary. Rated primary current is about what?
A 45.5 A
B 500 A
C 26.2 A
D 1100 A
Answer: C. 26.2 A. I=S/(β3V)=500 kVA/(β3Γ11 kV)β26.2 A.
A 500 kVA transformer has a 415 V three-phase secondary. Rated secondary current is about what?
A 120 A
B 500 A
C 696 A
D 1205 A
Answer: C. 696 A. I=500,000/(β3Γ415)β696 A.
Distribution conductor loss under balanced loading is proportional to what?
A Current squared
B Voltage only
C Frequency only
D Power factor angle only
Answer: A. Current squared. Copper loss is IΒ²R in each phase conductor.
Distribution transformer capacity is normally stated in what units?
A kW only
B kWh
C Hz
D kVA
Answer: D. kVA. Heating depends on voltage and current, so the nameplate uses apparent power.
A 100 kVA load at 0.8 power factor consumes how much real power?
A 20 kW
B 80 kW
C 100 kW
D 125 kW
Answer: B. 80 kW. Real power is kVA times power factor: 100Γ0.8=80 kW.
Along a loaded radial feeder, voltage magnitude generally does what with distance from source?
A Rises without limit
B Becomes DC
C Stays exactly fixed
D Falls
Answer: D. Falls. Series impedance causes voltage drop as load current flows.
In a four-wire feeder, neutral current is mainly due to what?
A Phase-load imbalance
B Balanced phase currents
C Line frequency
D Transformer core loss
Answer: A. Phase-load imbalance. Balanced phase currents cancel in the neutral; unbalanced components do not.
A three-phase four-wire system can supply which combination?
A Three-phase and single-phase loads
B Only DC loads
C Only balanced motors
D Single voltage only
Answer: A. Three-phase and single-phase loads. The neutral permits phase-to-neutral single-phase customers.
A ring-main network is often operated with one point open to obtain what?
A Two sources in parallel always
B Radial protection behavior
C Zero voltage drop
D DC operation
Answer: B. Radial protection behavior. An open point preserves an alternate path while normal fault protection remains simpler.
A normally open tie switch can connect a feeder to what during an outage?
A Alternate supply
B Ground permanently
C Customer meter
D Generator shaft
Answer: A. Alternate supply. Closing a tie can transfer load to a healthy neighboring feeder.
A load-break switch is designed to interrupt what?
A Any fault current
B Lightning current only
C Normal load current
D Transformer inrush always
Answer: C. Normal load current. It can switch specified load current but is not a fault-current breaker.
A disconnector or isolator is normally operated after what condition?
A Current is interrupted
B Fault current is flowing
C Load is at peak
D Voltage doubles
Answer: A. Current is interrupted. It provides visible isolation and is not intended to interrupt load or fault current.
Why does a feeder recloser attempt a brief reclosing after a trip?
A Fault may be temporary
B It measures kWh
C It raises voltage
D It changes phase order
Answer: A. Fault may be temporary. Many overhead faults clear after the initial interruption.
For fuse-recloser coordination, what is generally intended for a downstream lateral fault?
A All feeder breakers trip
B Lateral fuse clears first
C Upstream transformer trips first
D No protection operates
Answer: B. Lateral fuse clears first. Selective coordination keeps unaffected customers supplied.
A phase-balancing plan tries to distribute single-phase customers how?
A On one phase only
B On the neutral
C Across three phases evenly
D Across two frequencies
Answer: C. Across three phases evenly. Balanced loading reduces neutral current and phase voltage imbalance.
A distribution capacitor bank supplies which type of power locally?
A Mechanical power
B Fuel energy
C Short-circuit power only
D Reactive power
Answer: D. Reactive power. It provides capacitive VARs near inductive loads.
A 200 kW load at 0.8 power factor has apparent power equal to what?
A 250 kVA
B 160 kVA
C 200 kVA
D 360 kVA
Answer: A. 250 kVA. S=P/pf=200/0.8=250 kVA.
Why can low power factor raise feeder current for the same kW?
A Real power becomes zero
B Voltage doubles
C More apparent power flows
D Resistance decreases
Answer: C. More apparent power flows. Lower power factor requires larger current to deliver the same real power.
A feeder tie point is most useful when operators need to do what?
A Increase customer voltage indefinitely
B Measure conductor sag
C Restore loads after fault
D Change system frequency
Answer: C. Restore loads after fault. It lets a healthy section supply customers isolated from a faulted section.
How can an energy meter help a utility identify nontechnical loss?
A Measure pole height
B Compare billed energy
C Control line frequency
D Reduce conductor resistance
Answer: B. Compare billed energy. Metered sales can be compared with supplied energy to flag discrepancies.
Which operating change can reduce technical losses in a loaded feeder?
A Lower power factor
B Reduce unnecessary current
C Use thinner conductors
D Increase path length
Answer: B. Reduce unnecessary current. Loss falls with current squared, so efficient voltage and VAR management helps.