On a radial feeder, fault current usually decreases farther from the source because what increases?
A Path impedance
B Source voltage
C System frequency
D Transformer kVA
Answer: A. Path impedance. More conductor impedance separates the fault from the source.
Inverse-time overcurrent protection coordinates devices by what principle?
A All devices trip together
B Near faults trip faster
C Far faults trip first
D Voltage sets fuse color
Answer: B. Near faults trip faster. A downstream device is set to clear before an upstream backup device.
For a downstream lateral fault, what coordination helps keep the main feeder energized?
A Fuse-recloser coordination
B Transformer ratio matching
C Phase transposition
D Capacitor resonance
Answer: A. Fuse-recloser coordination. The lateral fuse can clear its branch before the upstream recloser locks out.
Approximate three-phase feeder voltage drop depends on I, R, X and what load quantity?
A Tower height
B Power factor angle
C Meter constant
D Pole count
Answer: B. Power factor angle. The common approximation uses √3I(Rcosφ+Xsinφ) for lagging current.
A line-drop compensator in a regulator adjusts voltage based on what estimate?
A Fuel temperature
B Line frequency
C Customer energy use
D Remote feeder drop
Answer: D. Remote feeder drop. It estimates voltage at a chosen point beyond the regulator.
An on-load tap changer changes transformer ratio while doing what?
A Carrying load current
B Disconnected from supply
C Shorting the winding
D Changing frequency
Answer: A. Carrying load current. An OLTC transfers between taps without interrupting customer supply.
How can distributed generation change normal radial feeder power flow?
A Remove all current
B Make it bidirectional
C Fix power factor at unity
D Eliminate voltage drop always
Answer: B. Make it bidirectional. Local generation can export power back toward the substation.
High rooftop PV output on a lightly loaded feeder can cause what?
A Voltage rise
B Frequency collapse always
C Zero neutral current
D Higher line resistance
Answer: A. Voltage rise. Reverse power flow and local injection may raise voltage near PV sources.
A switched capacitor bank may use voltage or power-factor measurements to control what?
A Conductor length
B System pole count
C Meter serial number
D VAR output
Answer: D. VAR output. Controls switch capacitor steps according to local reactive demand or voltage.
Why can capacitor banks create harmonic resonance with a feeder?
A They remove inductance
B LC impedance peaks
C They stop all harmonics
D They change line frequency
Answer: B. LC impedance peaks. Network inductance and capacitance can form a resonant circuit at a harmonic.
SAIDI measures average interruption duration per what?
A Customer over period
B Feeder kilometre
C Transformer phase
D Kilowatt-hour
Answer: A. Customer over period. It sums customer interruption durations and divides by customers served.
SAIFI measures average sustained interruption frequency per what?
A Transformer rating
B Customer over period
C Line section
D Meter reading
Answer: B. Customer over period. It counts customer interruptions and divides by customers served.
CAIDI is calculated as SAIDI divided by what?
A Peak demand
B Feeder length
C Transformer kVA
D SAIFI
Answer: D. SAIFI. CAIDI is average restoration time per sustained customer interruption.
A utility records 120 customer-hours interrupted for 60 customers. What is SAIDI?
A 0.5 hours/customer
B 60 hours/customer
C 2 hours/customer
D 120 hours/customer
Answer: C. 2 hours/customer. SAIDI=120/60=2 customer-hours per customer.
A system has SAIDI 6 hours/customer and SAIFI 3 interruptions/customer. What is CAIDI?
A 3 hours/interruption
B 6 hours/interruption
C 2 hours/interruption
D 18 hours/interruption
Answer: C. 2 hours/interruption. CAIDI=SAIDI/SAIFI=6/3=2 hours.
A normally open ring tie improves restoration by allowing what after isolation?
A Higher fault current always
B No switching
C Alternate feed path
D Frequency conversion
Answer: C. Alternate feed path. The healthy side can re-energize customers beyond the isolated fault.
Technical losses include which component?
A Conductor I²R loss
B Unbilled energy only
C Metering delay
D Incorrect customer record
Answer: A. Conductor I²R loss. Resistive losses in lines and transformers are technical losses.
Nontechnical losses can include which issue?
A Transformer copper heating
B Line corona
C Feeder resistance
D Unmetered energy use
Answer: D. Unmetered energy use. Theft, meter error and billing problems can cause nontechnical loss.
Phase unbalance can lead to which transformer or feeder concern?
A Zero line current
B Higher rated voltage
C Unequal phase currents
D No neutral current ever
Answer: C. Unequal phase currents. Uneven single-phase loads create different phase currents and extra heating.
Triplen harmonics in a four-wire network can cause what neutral effect?
A Cancel fully
B Reverse frequency
C Add in neutral
D Eliminate phase voltage
Answer: C. Add in neutral. Third-harmonic components are in phase across phases and can sum in the neutral.
A ground fault on a grounded distribution system is detected using what current component?
A Positive sequence only
B Load power factor
C Residual current
D Charging energy only
Answer: C. Residual current. Ground-fault protection senses imbalance or zero-sequence current.
During a close-in feeder fault, customer voltage commonly experiences what?
A Permanent frequency rise
B Voltage doubling
C Zero impedance
D Voltage sag
Answer: D. Voltage sag. Fault current through system impedance depresses voltage until cleared.
Why can coordinated protection improve reliability indices?
A Increases every outage
B Stops all load variation
C Eliminates maintenance
D Limits outage area
Answer: D. Limits outage area. Selective isolation keeps unaffected sections energized.
A distribution automation system can improve fault restoration by doing what?
A Locate and isolate sections
B Increase conductor sag
C Change AC to DC
D Disable relays
Answer: A. Locate and isolate sections. Sensors and switches help identify and isolate the faulted segment.
Demand response can reduce distribution stress by shifting what?
A Transformer polarity
B Customer load timing
C Line insulation
D System frequency source
Answer: B. Customer load timing. Moving flexible demand away from peak times reduces feeder loading.