Which fault connects one phase conductor to earth?
A Line-to-line fault
B Three-phase fault
C Single-line-to-ground fault
D Open-phase condition
Answer: C. Single-line-to-ground fault. A single-line-to-ground fault involves one phase and earth.
Which fault directly connects two phase conductors?
A Single-line-to-ground fault
B Three-phase-to-ground fault
C Open-circuit fault
D Line-to-line fault
Answer: D. Line-to-line fault. A line-to-line fault is a short circuit between two phases, with or without earth involvement.
Which short circuit involves all three phases?
A Three-phase fault
B Single-line fault
C Line-to-line fault
D Open-conductor fault
Answer: A. Three-phase fault. A three-phase short circuit involves all phase conductors and is treated as balanced.
A balanced three-phase fault has what phase relationship?
A Equal phase magnitudes
B Only one phase current
C Zero current in two phases
D Unequal phase angles
Answer: A. Equal phase magnitudes. Ideal balanced fault currents have equal magnitudes and are separated by 120 degrees.
Which sequence component appears in an unbalanced fault?
A Positive sequence only
B No sequence component
C Frequency sequence
D Negative sequence
Answer: D. Negative sequence. Unbalanced faults generally produce negative sequence; ground faults may also produce zero sequence.
Which fault type may clear itself after a brief arc?
A Permanent cable failure
B Winding short circuit
C Broken busbar joint
D Transient line fault
Answer: D. Transient line fault. Some overhead-line faults are temporary, and their arcs extinguish after brief de-energization.
What is the basic purpose of automatic reclosing?
A Raise the line voltage
B Restore service after transient faults
C Change relay pickup
D Balance transformer phases
Answer: B. Restore service after transient faults. Automatic reclosing attempts to restore a line after a temporary fault has cleared.
Which protection device is common on a small branch circuit?
A Distance relay
B Bus differential relay
C Generator synchronizer
D Fuse link
Answer: D. Fuse link. A fuse link provides simple overcurrent protection on many distribution laterals.
In an inverse-time relay, what happens as fault current rises?
A Operating time increases
B Operating time decreases
C Pickup current disappears
D Breaker rating doubles
Answer: B. Operating time decreases. Inverse-time relays generally operate faster at higher multiples of pickup current.
What does an instantaneous overcurrent element add?
A A fixed voltage boost
B A directional channel
C No intentional time delay
D A thermal reset heater
Answer: C. No intentional time delay. An instantaneous element can trip without intentional delay when current exceeds its threshold.
A definite-time overcurrent element operates after what?
A A delay that shrinks continuously
B A frequency reversal
C A manual reset only
D Set delay above pickup
Answer: D. Set delay above pickup. It trips after a preset delay once measured current exceeds pickup.
Why use directional overcurrent protection on a ring feeder?
A Measure transformer oil level
B Distinguish fault direction
C Synchronize two generators
D Limit charging current
Answer: B. Distinguish fault direction. Directional elements help coordinate protection when fault current can arrive from either direction.
A residual-current element commonly measures what?
A Average phase voltage
B Sum of phase currents
C Positive-sequence power
D Breaker travel time
Answer: B. Sum of phase currents. Residual current is the vector sum of phase currents and is near zero for balanced load.
A core-balance CT surrounds which conductors?
A Only the neutral bar
B The breaker trip coil
C One phase and earth
D All phase conductors
Answer: D. All phase conductors. Balanced live-conductor currents cancel in a core-balance CT, leaving residual current for detection.
What does a relay current setting establish?
A Pickup threshold
B Breaker contact gap
C CT insulation class
D Busbar thermal limit
Answer: A. Pickup threshold. The current setting determines when a relay element begins to operate.
What does a time-multiplier setting adjust?
A CT transformation ratio
B VT polarity
C Relay operating delay
D Breaker interrupting capacity
Answer: C. Relay operating delay. For inverse-time elements, the multiplier scales operating time while retaining curve shape.
Why coordinate an upstream relay with a downstream fuse?
A Make both trip together
B Raise feeder voltage
C Local device clears first
D Increase fault duration
Answer: C. Local device clears first. Coordination lets the device nearest the fault operate before upstream backup protection.
An isolator is normally operated after what condition?
A A fault is being cleared
B Breaker carries fault current
C Current is interrupted
D A relay measures impedance
Answer: C. Current is interrupted. An isolator provides visible separation and is generally not designed to interrupt load or fault current.
What is the role of an earthing switch?
A Ground isolated equipment
B Interrupt full fault current
C Measure residual current
D Adjust relay timing
Answer: A. Ground isolated equipment. An earthing switch grounds de-energized equipment after proper isolation.
What does an arc chute help a low-voltage breaker do?
A Measure load frequency
B Prevent relay pickup
C Extinguish contact arcs
D Cool transformer oil
Answer: C. Extinguish contact arcs. An arc chute divides and cools the arc formed as breaker contacts separate.
A low-voltage circuit breaker may combine which trip mechanisms?
A Thermal and magnetic
B Hydraulic and optical
C Chemical and acoustic
D Speed and torque
Answer: A. Thermal and magnetic. Many miniature breakers use thermal protection for overloads and magnetic protection for short circuits.
What does an undervoltage relay monitor?
A Voltage below a setting
B Current above a setting
C Power-flow direction
D Winding temperature
Answer: A. Voltage below a setting. An undervoltage element responds when measured voltage falls below its configured threshold.
What is a surge arrester designed to limit?
A Sustained overload current
B Transient overvoltage
C Power-frequency drift
D Breaker opening time
Answer: B. Transient overvoltage. A surge arrester limits transient overvoltage by diverting surge current to earth.
What can a transformer Buchholz relay detect?
A Line distance to fault
B Gas or oil-flow changes
C Generator reverse power
D Busbar phase sequence
Answer: B. Gas or oil-flow changes. A Buchholz relay responds to gas accumulation or sudden oil flow in a conservator-type oil transformer.
Why supervise a breaker trip circuit?
A Detect loss of trip readiness
B Increase the CT ratio
C Measure line charging power
D Control generator speed
Answer: A. Detect loss of trip readiness. Trip-circuit supervision identifies an open trip coil or wiring fault before protection is needed.